BGMJ Gas Filled Cylindrical Shunt Capacitors

Description

Gas-filled cylindrical shunt capacitors

BGMJ gas-filled dry capacitors use metallized polypropylene film in aluminium cans for low-voltage power factor correction. The three-phase model schedules cover 230V, 280V, 400V, 450V, 525V and 690V ratings. Match the complete model to the electrical duty, terminal configuration, case diameter, height and base stud.

230V and 280V group technical data

ParameterSpecification
Reference standardsGB12747-2004; IEC60831-1996; UL810-1995
Ambient temperature-25°C to +50°C
Relative humidity≤90%
Altitude≤2000m
Permissible voltageRated voltage continuously; 1.1 times rated voltage for 8 hours per day; 1.3 times rated voltage for 1 minute
Permissible current1.3 times rated current
Surge current≤300 times rated current
Reactive output tolerance-5% to +10%
Loss-angle tangent≤0.0015 at rated power-frequency voltage
Dielectric loss≤0.25W/kvar
Terminal-to-terminal withstand2.15 times rated voltage for 10s
Terminals-to-case withstand3000VAC for 60s

230V models

All model suffixes below belong to the BGMJ family. The listed -3 models use the three-phase Y1 outline. The drawing also identifies the YD1 single-phase alternative. ØD×H denotes case diameter and height; the stud column gives thread and projection.

BGMJ model suffixVoltage (kV)Output (kvar)Total capacitance (µF)Current (A)ØD×H (mm)Stud (mm)
0.23-3-30.2331817.576×180M12×16
0.23-4-3424110
0.23-5-3530112.6
0.23-6-3636115.176×210
0.23-7.5-37.545118.876×240
0.23-10-31060225.186×280
0.23-12-31272230.1
0.23-14-31484235.196×280M16×25
0.23-15-31590337.7
0.23-16-31696340.2

280V models

BGMJ model suffixVoltage (kV)Output (kvar)Total capacitance (µF)Current (A)ØD×H (mm)Stud (mm)
0.28-3-30.2831226.276×180M12×16
0.28-4-341628.2
0.28-5-3520310.3
0.28-6-3624412.476×210
0.28-7.5-37.530515.576×240
0.28-10-31040620.686×280
0.28-12-31248724.7
0.28-14-31456828.996×280M16×25
0.28-15-31560930.9
0.28-16-31665033

400V models

BGMJ model suffixVoltage (kV)Output (kvar)Total capacitance (µF)Current (A)ØD×H (mm)Stud (mm)
0.4-3-30.43604.376×135M12×16
0.4-4-34805.876×180
0.4-5-35997.2
0.4-6-361198.7
0.4-7.5-37.514910.8
0.4-10-31019914.476×240
0.4-12-31223917.3
0.4-14-31427920.276×280
0.4-15-31529821.7
0.4-16-31631823.186×280
0.4-18-31835826.0
0.4-20-32039828.9
0.4-25-32549736.1106×280M16×25
0.4-30-33059743.3116×280

450V models

BGMJ model suffixVoltage (kV)Output (kvar)Total capacitance (µF)Current (A)ØD×H (mm)Stud (mm)
0.45-3-30.45347.23.876×135M12×16
0.45-4-3462.95.176×180
0.45-5-3578.66.4
0.45-6-3694.47.7
0.45-7.5-37.51189.6
0.45-10-31015712.876×240
0.45-12-31218915.4
0.45-14-31422018.076×280
0.45-15-31523619.2
0.45-16-31625220.586×280
0.45-18-31828323.1
0.45-20-32031425.7
0.45-25-32539332.1106×280M16×25
0.45-30-33047238.5116×280

525V models

BGMJ model suffixVoltage (kV)Output (kvar)Total capacitance (µF)Current (A)ØD×H (mm)Stud (mm)
0.525-3-30.525334.73.376×135M12×16
0.525-4-3446.24.476×180
0.525-5-3557.85.5
0.525-6-3669.36.6
0.525-7.5-37.586.78.2
0.525-10-31011611.076×240
0.525-12-31213913.2
0.525-14-31416215.476×280
0.525-15-31517316.5
0.525-16-31618517.686×280
0.525-18-31820819.8
0.525-20-32023122.0
0.525-25-32528927.5106×280M16×25
0.525-30-33034733.0116×280

690V models

BGMJ model suffixVoltage (kV)Output (kvar)Total capacitance (µF)Current (A)ØD×H (mm)Stud (mm)
0.69-3-30.69320.12.576×135M12×16
0.69-4-3426.83.376×180
0.69-5-3533.44.2
0.69-6-3640.15.0
0.69-7.5-37.550.26.3
0.69-10-31066.98.476×240
0.69-12-31280.310.0
0.69-14-31493.611.776×280
0.69-15-31510012.6
0.69-16-31610713.4
0.69-18-31812015.186×280
0.69-20-32013416.7
0.69-25-32516720.9106×280M16×25
0.69-30-33020125.1116×280
Cylindrical shunt capacitor terminals and mounting outlines
Terminal arrangements, Y1 three-phase and YD1 single-phase outlines, and flange or stud fixing references.

Connections and ventilation

Use flexible cable with a temperature rating of at least 90°C. Connect each parallel capacitor through its own cable from the contactor side; do not use a capacitor terminal as the junction for feeding another capacitor.

Separate contactor feeds for parallel power capacitors
Separate capacitor feeds from the contactor, compared with an unsuitable looped terminal connection.

Provide bottom-to-top cabinet airflow. The ventilation guide uses approximately 2.5W/kvar for the combined capacitors, contactors, fuses and connections, or 8W/kvar when series reactors are included. These are cabinet heat-planning figures, not capacitor dielectric-loss ratings. The class-D ventilation example limits the air surrounding the capacitors to +55°C; use the selected unit's marked temperature category and service limits.

Cable selection guide

Values are conductor cross sections in mm². Al denotes aluminium and Cu copper. A dash means no value is listed. Check the final conductor choice against installation conditions and the selected terminal arrangement.

Output (kvar)Cable cross section (mm²)
230-240V400-480VAbove 600V
AlCuAlCuAlCu
5666666
7.510
101610
12.5——
15
20161010
2525161510
30—25
40352516
503525

Before access, isolate both main and control power, allow the initial 1-minute discharge delay, and verify that the capacitor is fully discharged before touching the terminals.