| Part Number: | ULO | - | HC04 | - | H32A | - | TE | H | - | 2L | - | M32 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Explanation: |
Manufacturer ULO - ULO Electronics |
Housing Series HC02 - Size 10A; use H10A |
Housing Size H10A - Size 10A, HC02, locking code 2B |
Cable Entry TE - Top entry; size 32A requires H |
Profile H - High profile; combine as TEH or SEH |
Locking 2B - Two opposing studs, sizes 10A or 16A only |
Entry Thread M20 - Sizes 10A or 16A, standard profile only |
These upper hoods provide cable-entry choices across the HC02 10A, HC03 16A and HC04 32A housing sizes. The 10A, 16A and 32A designations identify housing sizes. SE means side entry and TE means top entry; the added H identifies a high profile. Select the complete model and its listed thread suffix.
The 10A and 16A hoods have two opposing studs for a single locking arrangement. The 32A versions offer four studs for a double locking arrangement or two fitted metal latches. Match the hood dimensions, locking components and entry thread to the intended connector assembly.
| Model family | Entry and profile | Dimensioned height | Body length | Body width | Across studs | XX thread options |
|---|---|---|---|---|---|---|
| ULO-HC02-H10A-SE-2B-XX | Side; standard | 62mm | 63mm | 29.5mm | 72.5mm reference | M20, PG16 |
| ULO-HC02-H10A-SEH-2B-XX | Side; high | 67.5mm | 62.5mm | 72mm reference | M25, PG16, PG21 | |
| ULO-HC02-H10A-TE-2B-XX | Top; standard | 48mm, excluding entry boss | 63mm | M20, PG13.5 | ||
| ULO-HC02-H10A-TEH-2B-XX | Top; high | 67.5mm | 62.5mm | M25, PG16, PG21 |




| Model family | Entry and profile | Dimensioned height | Body length | Body width | Across studs | XX thread options |
|---|---|---|---|---|---|---|
| ULO-HC03-H16A-SE-2B-XX | Side; standard | 61.5mm | 80mm | 29.5mm | 88.5mm reference | M20, PG16 |
| ULO-HC03-H16A-SEH-2B-XX | Side; high | 70mm | 30mm | 89mm reference | M25, PG16, PG21 | |
| ULO-HC03-H16A-TE-2B-XX | Top; standard | 47.5mm, excluding entry boss | 29.5mm | M20, PG16 | ||
| ULO-HC03-H16A-TEH-2B-XX | Top; high | 70mm | 30mm | M25, PG16, PG21 |




All listed 32A bodies measure 82×56mm. The 2L versions measure 68mm across the fitted latches. Their movement drawings show 25mm swing extensions at each end for the standard SE profile and 23mm at each end for the high profiles.
| Model family | Entry | Profile | Body height | Locking components | XX thread options |
|---|---|---|---|---|---|
| ULO-HC04-H32A-SE-4B-XX | Side | Standard | 59.5mm | Four studs | M25, PG21 |
| ULO-HC04-H32A-SEH-4B-XX | High | 79mm | M32, PG21, PG29 | ||
| ULO-HC04-H32A-TEH-4B-XX | Top | M25, M32, PG21, PG29 | |||
| ULO-HC04-H32A-SE-2L-XX | Side | Standard | 59.5mm | Two metal latches | M25, PG21 |
| ULO-HC04-H32A-SEH-2L-XX | High | 79mm | M32, PG21, PG29 | ||
| ULO-HC04-H32A-TEH-2L-XX | Top | M25, M32, PG21, PG29 |






| Property | Applicable models | Specification |
|---|---|---|
| Body material | ULO-HC02-H10A-SE-2B-XX | Die-cast zinc alloy |
| Other models listed above | Die-cast aluminium | |
| Surface and colour | All listed models | Powder-coated; grey |
| Housing seal | 10A and 16A hoods | NBR |
| Latch material and finish | 32A 2L models | Metal; galvanized or nickel-plated finish |
| Temperature range | All listed models | -40°C to +125°C |
| Ingress protection | IP65 according to IEC 60529 for the coupled connector |